Brandt Instuments Representing Otis Instruments Fixed Gas Detection Systems, OI-6000 Wired & Wirefree Gas Detector Sensor Assembly for Fixed Gas Detection System
                    Brandt Instruments Representing Otis Instruments
   


Otis Instruments Fixed Gas Detection Systems Logo

Otis Instruments OI-6000
Remote Wired & WireFree™ Gas Sensor Assembly
with Display
Fixed Point Gas Detection Systems



home otis instruments fixed point detectors OI-6900 OI-6975 Gas Sensor Assembly With Display



 

Otis Instruments OI-6000 Wired & WireFree Gas Remote Sensor Assembly with Display

OI-6000 Remote Gas Sensor Assembly
with Display - Wired Or WireFree

The OI-6000 is an ambient air fixed point remote gas sensor assembly with a two-wire loop-power sensor assembly that can use Catalytic Bead, Electro-Chemical, PID, or Infrared sensor elements to detect a variety of gases including O2, H2S, SO2, NH3, Cl2, HF, PH3 as well as other toxic gases.

The OI-6000 comes standard with a 102x64 graphical LCD screen, three-button interface, non-intrusive magnetic switches, and the Otis-blue custom explosion-proof enclosure.  An optional internal-powered backlight is also available for the display.  Designed to reject EMI and other forms of interference in order to avoid false gas readings.

   Quickly setup and install a remote sensor
   Glass lid for viewing the display
   Non-intrusive calibration with MENU, ADD and SUB
   4-20mA and RS-485 Modbus output
   Explosion and weather proof Otis-Blue enclosure
   Broad choice of sensor elements available for gas detection
   Wired AC or battery DC power-in option
   Strobe alarms and horns would be managed by the controller
   Rapid response and clearing time

 

OI-6000 Remote Wired Sensor Assembly With Display
Technical Specifications

Enclosure Otis Blue explosion/flame proof
Size 6 " x 4.5" x 5" deep
Display Graphical LCD, sunlight readable (transflective), 102x64 resolution
Interface Three push buttons: MENU, ADD, SUB
Three corresponding magnetic switches for non-intrusive calibration
Sensor Options Electro-chemical, Catalytic Bead, Irfrared or PID:
H2S, O2, SO2, Cl2, H2, NH3, LEL (hydrocarbons), CO2, HCN, HF, CO, HCl, VOC's and more
Power Input 12-35 VDC, Current draw 250 mA (varies by configuration)
Signal Output 4-20mA (3-wire); RS-485 Modbus
Unit Radio Address 1 to 255
Unit Modbus Address 1-247
Certification CSA: Class 1, Div 1, Groups C & D T6 Ex D IIB, Zone 1 Aex D IIb T6
ATEX: II2 (1) GEx d mb [ia] OONT3
Relays Two dry contact (5 Amp) with 4 Amp fuses
Protection Power EMI filter, surge suppression, 4-20mA and RS-485 surge protection
Battery Type & Voltage 3.6 Volts DC, Lithium-Thionyl Chloride (Li-SOCl2) with connector
Warranty Hardware: One year (limited)
Sensor: varies with sensor type

OI-6000 Remote WireFree Sensor Assembly With Display
Technical Specifications

Enclosure Otis Blue explosion/flame proof
Size 6 " x 4.5" x 5" deep
Display Graphical LCD, sunlight readable (transflective), 102x64 resolution
Interface Three push buttons: MENU, ADD, SUB
Three corresponding magnetic switches for non-intrusive calibration
Power & Current Draw 12-35 VDC, Current draw 250 mA (varies by configuration)
Unit Radio Address 1 to 52 (1-78 for 2.4 GHz)
1-255 addresses per network
Relays Two 5 amp dry-contacts with 4 amp fuses
Sensor Options Electro-chemical or Infrared:
H2S, O2, SO2, Cl2, H2, NH3, LEL (hydrocarbons), CO2 and more
Power Input 12-35 VDC, Current draw 250 mA (varies by configuration)
Signal Output 4-20mA (3-wire); RS-485 Modbus
Radio Options

2.4 GHz ISM, 100 mW
900 MHz, 200 mW

Certification CSA: Class 1, Div 1, Groups C & D T6 Ex D IIB, Zone 1 Aex D IIb T6
ATEX: II2 (1) GEx d mb [ia] OONT3
Battery Type & Voltage 3.6 Volts DC, Lithium-Thionyl Chloride (Li-SOCl2) with connector
Warranty Hardware: One year (limited)
Sensor: varies with sensor type
   

OI-6000 IRLT Remote WireFree Sensor Assembly With Display
Technical Specifications

Enclosure Otis Blue explosion/flame proof
Size 6 " x 4.5" x 5" deep
Display Graphical LCD, sunlight readable (transflective), 128x64 resolution
Interface Three push buttons: MENU, ADD, SUB
Three corresponding magnetic switches for non-intrusive calibration
Unit Address 12-35 VDC, 100 mA (max)
Sensor Type Infrared: LEL
Power Input 12-35 VDC, Current draw 250 mA (varies by configuration)
Temperature -40° to 50° C
Relays Two configurable "Dry" contact (Form C) 6.3A @ 250 VAC, 5A @30 VDC
Output 4-20mA (3-wire); EIA-485 Modbus
Radio Options

2.4 GHz ISM, 100 mW
900 MHz, 200 mW

Certification CSA: Class 1, Div 1, Groups C & D T6 Ex D IIB, Zone 1 Aex D IIb T6
ATEX: II2 (1) GEx d mb [ia] OONT3
Battery Type & Voltage 3.6 Volts DC, Lithium-Thionyl Chloride (Li-SOCl2) with connector
Warranty Hardware: One year (limited)
Sensor: varies with sensor type

Otis Instruments OI-6000 Sensor Assembly Diagram

 

Otis Instruments OI-6000 Remote Gas Detector Assembly

Otis Instruments Replacement Gas Sensors
For Wired or WireFree™ Sensor Assemblies

Part # Description Range Resolution
Accuracy
OI-254-O2 O2, Oxygen 0 - 25% 0.1%
± 2%
OI-120-NP-17SHM LEL, Combustible Gas
(Catalytic Bead) (OI-6000 only)
0 - 100% LEL 1.0% Increments
±1%
OI-140-NP-IR-LEL LEL, Combustible Gas (Infrared)
(OI_6000 only)
0 - 100% LEL 1.0% Increments
± 2%
OI-254-CO CO, Carbon Monoxide 0 - 999 ppm 0.1 to 10 ppm, 1 ppm thereafter
± 2%
OI-140-IR-CO2 CO2, Carbon Dioxide
(OI-6000 only)
0 - 5% 0.1 ppm
± 2%
OI-254-H2S H2S,  Hydrogen Sulfide 0 - 100 ppm 0.1 to 10 ppm, 1 ppm thereafter
± 2%
OI-254-H2S-2K H2S, Hydrogen Sulfide (Ext.Temp) 0 - 100 ppm 0.1 to 10 ppm, 1 ppm thereafter
± 2%
OI-254-NH3 NH3, Ammonia 0 - 100 ppm 0.1 to 10 ppm, 1 ppm thereafter
± 5%
OI-254-NH3A NH3, Ammonia (Ext) 0 - 1000 ppm 0.1 to 10 ppm, 1 ppm thereafter
± 5%
OI-254-Cl2 Cl2, Chlorine 0 - 10 ppm 0.1 ppm
± 5%
OI-254-F2 F2, Florine 0-1 ppm 0.01 ppm
± 5%
OI-254-CH2O CH2O, Formaldeyde 0-10 ppm 0.01 ppm
± 2%
OI-254-H2 H2, Hydrogen 0- 4% 0.1 ppm
± 10%
OI-254-HCl HCN, Hydrogen Chloride 0- 30 ppm 0.1 ppm
± 5%
OI-254-HCN HCN, Hydrogen Cyanide 0- 30 ppm 0.1 ppm
± 5%
OI-254-HF HF, Hydrogen Floride 0 - 10 ppm 0.1 ppm
± 10%
OI-254-NO2 NO2, Nitrogen Dioxide 0-50 ppm 0.1 ppm
± 5%
OI-254-O3 O3, Ozone 0-100 ppm .1 to 10 ppm, 1 ppm thereafter
± 2%
OI-254-SO2 SO2, Sulfur Dioxide 0 - 20ppm .1 to 10 ppm, 1 ppm thereafter
± 2%
OI-254-PH3 PH3, Phosphine 0 - 20 ppm 0.1 ppm
± 2%
OI-254-PID-A1 PID, Photo Ionization Detector for volatile organic compounds (VOCs) (OI-6000 only) 10, 20 or 50 ppm 0.1 to 10 ppm, 1 ppm thereafter
± 5%
OI-254-AH PID, Photo Ionization Detector for volatile organic compounds (VOCs) (OI-6000 only)

1000 or 2000 ppm

0.1 to 10 ppm, 1 ppm thereafter
± 3%


Note: Other gases and ranges available
. Contact us for additional information

Green_Back-To-Top_Icon


WARNING! Otis Instruments equipment should only be used in conjunction with the manufacturer's instructions.
Failure to follow such instructions could result in serious injury or fatalities.

 

Return to Brandt Instruments
For more information  Email Mail
Brandt Instruments, Inc. 
    18568 Oak Grove Parkway 
    Prairieville, LA  70769 
1-800-337-6291  
Phone: 225-673-6776
    Fax: 225-673-6725
 

Visa, MC, AmEx, Discover Cards

Copyright © 2002-2017 Brandt Instruments, Inc.